3 Phase Industrial Low Frequency UPS 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA
Product Details:
Place of Origin: | China |
Brand Name: | ZGDUPS |
Certification: | CE |
Detail Information |
|||
Rated Voltage: | 380/400/415 Vac Three-phase | Frequency Range: | 45-65Hz |
---|---|---|---|
Protection Degree: | IP20 | Efficiency Smart Mode: | Up To 98% |
Capacity: | 8KW 12KW 16KW 24KW 32KW 48KW 64KW 80KW 96KW 128KW 160KW | Power: | 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA |
High Light: | Low Frequency UPS 80KVA,60KVA Low Frequency UPS,Electromedical Equipment Low Frequency Online UPS |
Product Description
Industrial Low Frequency Ups 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA 3 Phase
The control panel consists of LED status indicator and 7-inch touch screen Status indicator:
The LED indicator on the control panel provides fast information, and the LED may be on, flashing or off in different states. There are five on the panel
THREEPHASE OUTPUT | |||||||
Rated power [kVA] | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
output active power [kW] | 8 | 12 | 16 | 24 | 32 | 48 | 64 |
Power factor range | |||||||
100 % load | 0,5+0,8 IND | ||||||
100^80%load | 0,8+1 IND | ||||||
80% load | 1+0,8 CAP | ||||||
70% load | 0,5+0,8 CAP | ||||||
80% load | computer | ||||||
efficiency with standard UPS full load |
90 | 90 | 91 | 91 | 92 | 92 | 92 |
half load | 88 | 88 | 89 | 89 | 90 | 91 | 91 |
loss power with nominal load and battery charge kW / kcal /B.T.U. |
0,89~ 800 4367 |
~1,33 1100 4400 |
~1,58~ 1400 5560 |
~~2,37~~ 2000 7940 |
2,78~ 2400 9500 |
~417~~ 3600 14000 |
~5,57~ 4800 19000 |
flow rate allowing (for room installation) (*) [mc/h] |
496 | 682 | 868 | 1240 | 1488 | 2232 | 2976 |
leakage current (mA) max. | 300 | ||||||
MTBF: | 200.000 hours. | ||||||
remote signalling | three tension free exchange contacts (battery low, battery discharging, by-pass/fault); output 12Vdc 80mA |
||||||
remote command | EPO and bypass | ||||||
computer interface | RS232/C | ||||||
operating temperature | 0 + + 40 °C | ||||||
relative humidity max. | 95% (without condensate) | ||||||
maximum operating altitude | 1000 m at rated power An (-1% An for each 100m over 1000 m) max 4000 m | ||||||
cooling | forced ventilation (fan speed function of the load) | ||||||
acoustic noise, as measured at 1m from front of equipment (depend on load and temperature) dBA |
48 + 54 53 + 60 | 53 + 62 | |||||
degree of protection | IP20 | ||||||
cable input | bottom | ||||||
Accessibility to maintenance | front/upper/right side | ||||||
Applicable Standards |
Safety EN 62040-1-1, Electromagnetic Compatibility EN 50091-2 (restricted sales distribution)(**) |
||||||
standard | BACKFEED PROTECTION | ||||||
optional |
harmonic reduction filter/12 pulse rectifier, insulation transformer on bypass line (external cabinet) |